Brunton Thermostats - Type ETN |
|
|
|
|
Print page |
| |
|
Thermostat with setback mode
Electronic on /off control up to 16 A / 3600 W.
Built-in setback mode for automatic comfort and setback temperature via remote timer.
Delivered incl. floor sensor or remote room sensor.
For DIN-rail mounting. |
|
|
| |
|
Product programme
| With 16 amp S.P.S.T. contact, fed from the thermostat supply voltage: |
|
Interrupter |
Sensor |
Type |
|
Yes |
Without sensor |
ETN-2P-1441 |
|
Yes |
With floor sensor |
ETN/F-2P-1441 |
|
Yes |
With room sensor |
ETN/F-2P-1449 |
|
|
|
No |
Without sensor |
ETN-1441-P |
|
No |
With floor sensor |
ETN/F-1441-P |
|
No |
With room sensor |
ETN/F-1449-P | ETN is also available for 24V and 115V AC. |
|
|
| |
|
THERMOSTAT FUNCTIONS
Thermostat control: Type ETN is an electronic on/off thermostats with control of temperature by means of NTC sensor. Red LED indicates when heating is on.
Temperature setback: Type ETN is with setback mode, which is activated with a day/week timer, e.g. MM-7595. The timer is programmed with the required comfort and setback periods. The setback mode of type ETN can be adjusted +3/+10°C.
Type ETN with setback mode can be connected to a day/ week timer, which is programmed with the required comfort and setback periods.
Built-in 2-pole interrupter: Type ETN is with built-in 2-pole interrupter, which can disconnect the power to the heating system. |
|
|
| |
|
Mounting
Mounting of the thermostat DIN-rail mounting in a switchboard. A cover box for separate wall mounting is available.
Type of temperature sensor: Delivered incl. floor sensor or incl. remote room sensor.
Mounting of floor sensor: Floor sensor is used for comfort heating of floor. The sensor is mounted in conduit of consideration of replacement. The conduit is mounted between heating cables and ended towards the floor surface. If required, the floor sensor can be extended up to 100 m with a standard installation cable.
Mounting of room sensor:
Room sensor is used for room heating. The room sensor is mounted approx. 1.6 m above the floor. Draught, direct sunlight or any other direct heating outlet must be avoided. |
|
|
| |
|
Technical data
|
Voltage |
230V AC |
|
Power consumption |
3VA |
|
S.P.S.T. switch ETN, ETN-2P |
16A / 250V |
|
S.P.C.O. switch (volt-free ETN-P) |
10A / 250V AC |
|
Temperature scale |
0 / +35°C |
|
Temperature differential |
+0.3 / +6°C |
|
Setback temperature |
+3 / +10°C |
|
Setback temperature (ETN-1442) |
+6 / +20°C |
|
Ambient temperature |
-20 / +50°C |
|
Housing / protection |
IP 20 | ETN thermostat is maintenance free.
Accessories
|
Description |
Order |
|
Cover box for wall |
ETNK |
|
Floor sensor |
ETF-144/99A |
|
Room sensor |
ETF-944/99-H | |
|
|

|
 |
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
|
|